BCNet-FX-S is used for PLC Ethernet data acquisition of Mitsubishi FX1S/1N/2N/3S/3G/3GA/3GC/3U/3UC series, Inovance, Shilin AX, Hechuan, Weikong, etc. It is very convenient for construction and production management system. The module integrates WiFi function, supports AP mode, STA mode and AP+STA mode, which is very convenient to build a WiFi network, and perform PLC programming and data collection directly through WiFi. It does not occupy the PLC programming port. While the host computer monitors the PLC data through the Ethernet, the touch screen can communicate with the PLC through the multiplexing interface X2. Support the vast majority of SCADA software in the field of industrial control, support Mitsubishi MC Ethernet protocol and ModbusTCP master-slave communication. Support point table detection function.
BCNet-FX-S function
- Installed on a 35mm guide rail, no external power supply required. The COM1 port is connected to the S8 programming communication port of FX, and the COM2 expansion port is used for touch screen communication.
- Through the WEB server or the configuration diagnostic tool BCDevice, the device can be parameterized and run diagnostics.
- Automatically adjust the baud rate of the FX programming communication port, which can meet the needs of large data communication.
- Integrated WiFi function, support AP mode, STA mode and AP+STA mode.
- PLC programming and data acquisition can be performed through WiFi.
- Support Ethernet communication of MELSOFT products (GX Works2, GX Developer, etc.).
- Support the communication of the host computer MC Ethernet protocol (MELSEC Communication Protocol), and support the access of the host software (Kingview, MCGS, Force Control, IFIX, INTOUCH, KepWare OPC server, etc.).
- Integrated ModbusTCP server, support FC1, FC2, FC3, FC5, FC6, FC16, Modbus data area is automatically mapped to FX data area.
- With MC communication protocol, programming in advanced languages (such as VB, VC, C#, etc.) can be realized, and data communication with Mitsubishi FX can be realized, which is convenient for the development of production management system.
- The SCADA (host configuration software) supporting OPC channel communicates with FX in OPC mode.
- It can realize MELSOFT connection, MC protocol connection, ModbusTCP connection mode at the same time, and support the connection of 32 upper computers.
- Support firmware update on the user side through Ethernet, one purchase, permanent upgrade.
Typical Application

Product number | BCNet-FX-S |
---|---|
Describe | Mitsubishi FX series PLC Ethernet communication processor |
Color | Metallic Black |
Status Display | Pwr,COM1,COM2,WiFi |
Ethernet interface Interface Type output rate Protocol support Number of TCP connections | Link/Active indicator, automatic polarity crossover RJ45 female socket 10/100Mbps MELSOFT, MC, ModbusTCP up to 32 |
WiFi interface Interface Type transmit power Receive sensitivity Wireless type Security Mechanism Protocol support number of connections | 802.11 b/g/n 2.4G-2.5G External high gain antenna +26dBm(MAX,2.4G 802.11b/g/n) -89dBm(802.11b), -74dBm(802.11g), -72dBm(802.11n) Station/AP mode WPA-PSK/WPA2-PSK/WEP MELSOFT, MC, ModbusTCP up to 32 |
X1 interface (connected to PLC) Interface Type Transmission rate Protocol support | RS422 MD8 communication female port 9.6K, 19.2K, 38.4K, 115.2Kbps FX programming port |
X2 interface (with HMI) Interface Type Transmission rate Protocol support | RS422 MD8 communication female port 9.6K, 19.2K, 38.4K, 115.2Kbps FX programming port |
Programming software Configuration Software OPC software | GX Works2 Kingview, 3D Force Control, etc. KepWare OPC |
Diagnostics and Parameter setting | IE browser, default 192.168.1.178, BCDevice |
Power supply Voltage type | FX communication port to take power directly (communication cable) or external 24VDC 24VDC/100mA |
Operating temperature | 0~60℃ |
Working humidity | 90% non-condensing |
Installation method | 35mm rail installation |
Electromagnetic Compatibility | 2014/30/EU |
Anti-vibration | 4.5mm/30Hz/10Min |
ESD | 6KV |
Factory aging | The 60-degree aging box runs for 168 hours, and the power is turned on and off 500 million times |
Communication stability | Continuous communication with PLC for 30 days, 130 million times of communication with 0 errors |
Certification | CE Certification |
Dimensions (LWH) | 90*24*65mm |
Weight | 100g |