HJ5208 Hardware Manual

Contents

HJ5208 Hardware Manual Version V1.2

Hardware parameters

Specification

Processor32-bit low-power processor
Network3 port 10M/100M
RS4852 channel
input powerDC 9~28V
Power consumption4W
Operating temperature-20~70°C
Storage temperature-30 ~85°C
Working humidity5 – 95%RH
CertificationFCC/CE

Network parameters

Interface speed10/100M Auto
Electrical isolation2KV
Network ProtocolIP/TCP/UDP/DHCP/DHCPD/DNS/HTTP/SNMP
Maximum number of connections1024

RS485 Parameters

Number of ports2
Baud rate300~230400BPS
Data bits5/6/7/8 Bits
Stop bit1/2 Bits
CheckNone/Odd/Event
Buffer4MBytes
InterfacePort 1(A1,B1)/Port 2(A2,B2)

Digital input

Number of channels8
Input typeOptical isolation PNP/NPN
Rated voltage24V
Input Current0.05A
Response time1 ms
ProtectOvercurrent and overvoltage

Digital output

Number of channels8
Output typePNP
Rated voltage24VDC
Output Current0.05A
Response time1 ms

Analog input

Number of channels8
Input type0~20mA/0~5V/0~10V(Optional)
Precision0.1%
Sampling time1 ms
Input resistance50R(current)/1M ohm(voltage)
ProtectOvercurrent

Analog output

Number of channels4
Output type0~20mA/0~5V/0~10V(Optional)
Precision0.1%
Sampling time1 ms
Output impedance50R(current)/100R(voltage)
ProtectOvercurrent

Terminal wiring diagram

HJ5208 (8 PNP/NPN Inputs/8 Output/8 Anglog Input/4 Anglog Output)

Digital input wiring method

CM1, DI/0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7 are grouped into a group, CM2, DI/1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7 are grouped into a group, the common terminal CMx (x value 1, 2, 3, 4) is connected to 0V or 24V. If the common terminal is connected to 0V, the output type of the input DI point connection is PNP mode. If the common terminal is connected to +24V, the output type of the input DI point connection is NPN mode.

how to connect the PNP input type:

how to connect the NPN input type

PNP Output wiring method

M1, DQ0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 24V are a group, the common terminal M1 is connected to 0V, and the 24V power terminal is connected to +24V of the power supply.

Analog output wiring method

Note: Two-wire output wiring, AQ point is connected to P+ of the input device, and P- of the input device is connected to 0V.

Leave a Comment