HMI-S71200(SMART screen connected to S71200/1500)

Siemens SMARTLINE touch screen has a high cost performance, but can only be used to connect S7-200. HMI-S71200 is a protocol conversion gateway for Siemens PLC with Ethernet interface (S7-1200, S7-1500, S7300PN, etc.) and Siemens SMART IE touch screen Ethernet communication.
HMI-S71200 has two physical interfaces, LAN1 and LAN2 respectively have independent local area network capability. The LAN1 port is a dual RJ45 port with switch function, which is mainly used to connect PLC; the LAN2 port is a single port RJ45 port, which is mainly used for the connection of SMART IE touch screen.

HMI-S71200 function

  1. Installed on a 35mm guide rail, LAN1 is a dual-port RJ45 with switch function, and this port is connected to PLC; LAN2 is a single-port RJ45, which can be connected to a SMART IE touch screen; HMI-S71200 needs an external 24VDC power supply;
  2. Integrate the WEB server, through the webpage, you can set the device parameters and run diagnosis; you can also configure it through the BCDevice tool; you can configure it from the LAN1 or LAN2 port at will;
  3. Realize the NAT function, map the IP address and port number of the PLC connected to the LAN1 port to any IP and port number of the LAN2 port;
  4. The SMART IE series touch screen can be connected to S7-1200, S7-1500, S7300PN and other PLCs;
  5. Support up to 32 LAN2/LAN1 server/client concurrent models, LAN2 port can support up to 8 SMART IE touch screen connections;
  6. Support firmware update on the user side through Ethernet, provide firmware with more functions for free, buy hardware once, and upgrade permanently.

Application

Technical Parameter

Product numberHMI-S71200
DescribeSiemens PLC Ethernet communication processor
ColorMetallic Black
Status DisplayPwr,LAN1,LAN2
Ethernet interface
Interface Type
Transmission rate
Protocol support
Number of TCP connections
IEEE 802.3 compatible, Link/Active indicator, line sequence adaptive, support Auto-MDIX
RJ45 female socket
10/100Mbps
S7TCP (SMART IE touch screen)
32
LAN1 interface (connected to PLC)
Interface Type
Transmission rate
Protocol support
Ethernet
RJ45*2
10/100M
S7TCP
LAN2 interface (connected to upper position)
Interface Type
Transmission rate
Protocol support
Ethernet
RJ45*1
10/100M
S7TCP (SMART IE touch screen)
Touch ScreenSiemens SMART IE touch screen
Diagnostics and Parameter settingIE browser, default 192.168.2.188 (LAN1), default 192.168.1.188 (LAN2)
BCDevice Configuration Tool
Power supply
Voltage type
External 24VDC
24VDC/100mA
Operating temperature0~60℃
Working humidity90% non-condensing
Installation method35mm rail installation
Electromagnetic Compatibility2014/30/EU
RoSH Productionyes
Anti-vibration4.5mm/30Hz/10Min
ESD6KV
Factory agingThe 60-degree aging box runs for 168 hours, and the power is turned on and off 500 million times
Communication stabilityContinuous communication with PLC for 30 days
CertificationCE Certification
Dimensions (LWH)90*24*65mm
Weight120g