General parameters
Installation mode | DIN 35 guide rail or screw fixed |
Operating temperature | 0 °C ~ 50 °C |
Storage temperature | 20 °C ~ 60 °C |
Operating humidity | 10% RH ~ 90% RH (no condensation) |
Air requirements | Non-corrosive, no dust |
Operating Voltage | DC24V ±10% |
Working Current | < 1A |
Programming software | Gx-developer/gx-works 2 |
Maximum procedural steps | 32,000 steps |
Port 0 | RS232: Program Download, man-machine interface communication; Programming Port Protocol, the default baud rate of 19200 |
Port 1 | RS485: man-machine interface communication, all kinds of instrument communication; Default port protocol, default baud rate 19200, optional MODBUS- RTU/RS/RS2 protocol |
Port 2 | RS485: man-machine interface communication, all kinds of instrument communication; default programming port protocol; Default baud rate 19200, optional MODBUS-RTU/RS/RS2 protocol. |
Port 3 | Can: Our PLC internal networking use |
Digital input | DC24V NPN leak |
Digital output | Transistors: DC24V NPN leaky (500mA) ; Relay: dry electrocution (AC250V/DC30V, 3A) |
Analog input | Default 0-10V Optional 0-20mA NTC 10K (-40 °C ~ 150 °C) NTC 50k (-40 °C ~ 210 °C) |
Analog output | 0-10V |
Communication pin definition
9Pin Female | Pin Number | RS-232 | RS-232 |
Port 1 | 1 | ||
2 | TX | ||
3 | RX | ||
4 | |||
5 | GND | GND | |
6 | |||
7 | |||
8 | |||
9 |
9Pin Female | Pin Number | RS-485(1) | RS-485(1) | RS-485(2) | RS-485(2) | CAN | CAN |
Port 2*1 | 1 | A+ | |||||
2 | CANL | ||||||
3 | CANH | ||||||
4 | |||||||
5 | GND | GND | GND | GND | GND | GND | |
6 | B- | ||||||
7 | |||||||
8 | B- | ||||||
9 | A+ |
The connection between the RS-485 communication ports is A+ to A+, B- to B-; if more than 2 devices are networked, a 120R terminal resistor needs to be matched.
The wiring between the CAN communication ports is CANH to the extension module CANH (multiple modules are connected together), CANL is connected to the extension module CANL (multiple modules are connected together), please be sure to use a shielded communication line to connect, and the length is not more than 500mm. If more than 2 devices are networked, a 120R terminal resistor needs to be matched.