XCNet-MB-S(Profinet to ModbusRTU)

XCNet-MB-S is a high-performance protocol conversion gateway, which can realize Siemens PLC with Ethernet interface (S7-1200/1500, S7-300PN, S7200 SMART, etc.), Siemens Ethernet module (CP243-1, CP343- 1, etc.) ModbusRTU serial communication and ModbusTCP master-slave communication. The module integrates WiFi function, supports AP mode, STA mode and AP+STA mode, which is convenient for building WiFi network, PLC programming, data acquisition and data exchange can be performed through WiFi.
XCNet-MB-S supports two-way ModbusRTU master-slave communication, without PLC programming, without GSD file import, convenient for DCS system collection, instrument data reading, etc.
The LAN/WiFi of XCNet-MB-S integrates ModbusTCP and BCNetS7 server communication functions, and the Modbus mapping relationship can be edited freely; it integrates data exchange functions, and supports data exchange between Siemens S7-1200/1500 and SMART S7-200 and other network port PLCs; Integrated ModbusTCP client function, supports reading and writing ModbusTCP slave devices, without PLC programming.

XCNet-MB-S Features:

  1. Installed on a 35mm guide rail, LAN is three RJ45 ports, with switch function, LAN is connected to PLC, touch screen and host computer; X1 and X2 are RS485 serial bus interfaces; WiFi external high-gain antenna can be connected to the host computer ; XCNet external 24VDC power supply;
  2. Integrated WEB server, device parameters and operation diagnosis can be set through the webpage; it can also be configured through the BCDevice tool; it can be configured arbitrarily from LAN or WiFi;
  3. Support two-way serial ModbusRTU master-slave communication, which can extend the ModbusRTU serial bus to S7-1200, S7-1500, S7200 SMART and other network port PLCs, without PLC programming or GSD file import;
  4. Support ModbusTCP server function, which can map LAN-connected PLC to ModbusTCP server with LAN/WiFi interface;
  5. Support data exchange function, which can realize data exchange between Siemens network port PLC, Siemens network port PLC and ModbusTCP device data exchange, ModbusTCP instrument data reading, without PLC programming;
  6. Support the BCNetS7 protocol server function, which can map the PLC connected by LAN to the BCNetS7 protocol server of the LAN/WiFi interface;
  7. Integrated WiFi function, support AP mode, STA mode and AP+STA mode;
  8. PLC programming, data acquisition and data exchange can be performed through WiFi;
  9. Realize the connection of SmartIE series touch screen to PLCs such as S7-1200 and S7-1500;
  10. The LAN/WiFi interface can support up to 32 host computer access;
  11. SCADA (upper configuration software) that supports OPC channel communicates with PLC in OPC mode;
  12. Support firmware update on the user side through Ethernet, provide firmware with more functions for free, buy hardware once, and upgrade permanently.

Application:

Technical Parameter

Product numberXCNet-MB-S
DescribeProfinet to ModbusRTU/ModbusTCP Gateway
ColorMetallic Black
Status DisplayPwr,Bus,LAN,WiFi
X1 interface
Interface Type
Transmission rate
Protocol support
RS485
terminal
2.4K, 4.8K, 9.6K, 19.2K, 38.4K, 57.6K, 115.2K, etc.
ModbusRTU slave station, ModbusRTU master station
X2 interface
Interface Type
output rate
Protocol support
RS485
terminal
2.4K, 4.8K, 9.6K, 19.2K, 38.4K, 57.6K, 115.2K, etc.
ModbusRTU slave station, ModbusRTU master station
LAN interface
Interface Type
Transmission rate
Protocol support
number of connections
Link/Active indicator, automatic polarity crossover
RJ45 female socket*2, RJ45 female socket
10/100Mbps
S7TCP, ModbusTCP master-slave, BCNetS7
up to 32
WiFi interface
Interface Type
transmit power
Receive sensitivity
Wireless type
Security Mechanism
Protocol support
number of connections
802.11 b/g/n 2.4G-2.5G
External high gain antenna
+26dBm(MAX,2.4G 802.11b/g/n)
-89dBm(802.11b), -74dBm(802.11g), -72dBm(802.11n)
Station/AP mode
WPA-PSK/WPA2-PSK/WEP
S7TCP, ModbusTCP, BCNetS7
up to 32
Programming software
Configuration Software
OPC software
Portal V16
WinCC, IFIX, INTOUCH, etc.
KepwareOPC
Diagnostics and Parameter settingIE browser, default 192.168.1.188、BCDevice
Power supply
Voltage type
External 24VDC
24VDC/100mA
Operating temperature0~60℃
Working humidity90% non-condensing
Installation method35mm rail installation
Electromagnetic Compatibility2014/30/EU
RoSH Productionyes
Anti-vibration4.5mm/30Hz/10Min
ESD6KV
Factory agingThe 60-degree aging box runs for 168 hours, and the power is turned on and off 500 million times
Communication stabilityContinuous communication with PLC for 30 days
CertificationCE Certification
Dimensions (LWH)115*27*75mm
Weight150g